Delaware Energy Code Update: Key Changes Under the 2024 IECC

Delaware Energy Code Update: Key Changes Under the 2024 IECC

Delaware officially adopted the 2024 International Energy Conservation Code (IECC) on April 11, 2026 after a lengthy and closely watched regulatory process. The final adoption is consistent with a standard update, even though the original proposal was significantly more ambitious, with provisions aimed at “future-ready” and “zero net energy capable” residential construction. The state ultimately scaled back those requirements, adopting a 2024 IECC baseline along with two additional appendices: electric vehicle charging infrastructure for low-rise residential projects and solar readiness for commercial buildings 5 stories or less as well as 4 and 5-story multifamily buildings. 

A Long and Unusual Code Update Process 

In 2025, Delaware’s Department of Natural Resources and Environmental Control (DNREC) proposed an energy code update corresponding with previously adopted state policy calling for “zero net energy capable” residential construction by the end of 2025.  This policy was created by a 2009 state law that states:  

“As of December 31, 2025, all new residential building construction in the State of Delaware shall be zero net energy capable. As of December 31, 2030, all new commercial building construction must also be zero net energy capable.” 

“Zero net energy” refers to a building that produces as much energy as it consumes over a given period, typically through a combination of efficiency measures and on-site renewable energy. “Zero net capable” means the building is designed so it could reach net zero in the future with additional upgrades, such as added renewable energy or system improvements. 

This concept is often misunderstood, as it does not mean that all buildings are required to be net zero at the time of construction. That language, however, led many in the design and construction industries to expect a major shift in building requirements, on a tight timeline for implementation. 

Concerns Emerge from Industry Stakeholders 

A variety of stakeholders, ranging from architects and engineers to developers and builders, expressed concerns about the feasibility and unintended detrimental effects the proposed changes would have on the state’s building industry. The Home Builders Association of Delaware (HBADE) strongly opposed the proposed energy code, advocating for more moderate changes. Some common concerns voiced included increased construction costs, housing affordability impacts, grid and utility readiness, and administrative and enforcement complexity. 

In October of 2025, DNREC Secretary Gregory Patterson declined to approve the regulation, citing the above concerns. As a result, the DNREC was forced to pause the adoption and reconsider its proposal. What was expected to be a straightforward adoption became a multi-stage review process, including providing additional public comment periods. 

What Delaware Actually Adopted 

The original proposal was revised and significantly narrowed. The adopted code baseline remained the 2024 IECC for residential buildings and the 2024 IECC in combination with ASHRAE 90.1-2022 for commercial and mid-high rise multifamily buildings, becoming effective immediately on April 11, 2026. However, most “future-ready” and “zero net energy capable” requirements were removed or significantly reduced from the original proposal. That included the removal of most of the appendices. The final adopted code retained only two appendices: 

  • Appendix RE – EV Charging Infrastructure (Residential projects)  
  • Appendix CB – Solar-Ready Zone (Commercial and mid-high rise multifamily projects) 
Local Implementation and Enforcement Timing 

Delaware uses a statewide energy code framework, meaning the state establishes the code and local jurisdictions are responsible for enforcement. 

Local jurisdictions have up to 12 months to fully implement enforcement procedures from the April 11 adoption date. 

This can create varying timelines for enforcement across municipalities, as the DNREC works to prepare updated materials and training for builders and code officials. 

What The DE Code Update Means for Project Teams 

Although Delaware’s final adoption is more moderate than the original proposal, the code change from 2018 to 2024 IECC is still very significant.  

Key Changes to the Delaware Residential Energy Code   

The following are key changes that design, development, and construction professionals will need to plan for when working on low-rise residential buildings three stories or less, including one- and two-family dwellings, townhouses, and multifamily buildings.

1. Sampling Permitted in Testing (Sections R402.5.1.2, R403.3.9, R403.6.4)

The 2024 IECC introduces sampling as an option for certain required tests in multifamily buildings containing 8 or more units. This applies to: 

  • Building envelope air leakage (blower door) testing 
  • Duct leakage testing 
  • Mechanical ventilation testing 

To use the sampling approach, projects must follow specific testing protocols: 

  • Building must contain at least 8 dwelling units 
  • Testing must be performed on the greater of 7 units or 20% of the total units 
  • Sample must include a top-floor unit, a ground-floor unit, a middle-floor unit, and the unit with the largest testing unit enclosure area 
  • If a tested unit fails, 3 additional units must be tested, including retesting the unit that failed

Sampling can help streamline the testing process for qualifying multifamily projects by reducing the number of individual units that need to be tested. Project teams should familiarize themselves with the sampling protocols early to ensure testing requirements are met. ReVireo employs professionals with the required credentials to perform the testing and verification services.

2. Mandatory Duct Leakage Testing Thresholds (Section 403.3.7)

The 2024 IECC establishes mandatory total duct leakage testing requirements that apply regardless of the residential compliance pathway selected. Section R403.3.7 requires duct systems to be tested, with maximum allowable leakage rates established in Table R403.3.8. 

The allowable leakage varies depending on factors such as whether the HVAC equipment is installed, whether the ductwork is located entirely within conditioned space, and the size and configuration of the duct system. This makes proper duct installation and sealing particularly important, as projects must demonstrate compliance through testing.  

Early coordination between mechanical contractors, builders, and testing professionals is critical to help identify potential issues before testing.  

2024 IECC Residential Maximum Total Duct Leakage Thresholds  

  < 3 Returns Ducts > 3 Return Ducts 
Ducts in unconditioned space 
No Air Handler  3%  4% 
W/ Air Handler  4%  6% 
Ducts in 100% conditioned space 
No Air Handler  6%  8% 
W/ Air Handler  8%  12% 

 

3. Mechanical Ventilation & Exhaust Fans (Section R403.6.2)

The 2024 IECC expands requirements for mechanical ventilation fan efficiency, airflow testing, and exhaust fan controls: 

  • Fan efficiency: Minimum efficiency requirements now apply to mechanical ventilation and outdoor air ventilation fans. 
  • Testing: The updated code expands testing requirements to include all mechanical ventilation systems, as well as all supply and exhaust fans, including bathroom and kitchen exhaust fans. 
  • Bathroom exhaust controls: Intermittent bathroom exhaust fans must have automatic shutoff controls, such as a timer, occupancy sensor, humidity sensor, or contaminant control. An exception applies to qualifying fans that are part of the home’s mechanical ventilation system. 

These requirements make it important to consider ventilation equipment, controls, and testing needs during design and installation. 

4. Lighting Efficacy and Controls (Sections R404.2.2,R404.2.1,R404.2.2,Table R404.1)

The updated code establishes specific efficacy requirements for permanently installed lighting.  

Key changes include:  

  • Lighting Efficacy: Permanently installed lighting must provide at least 45 lumens per watt or contain lamps capable of operating at an efficacy of at least 65 lumens per watt. 
  • Habitable Spaces: Interior lighting controls have also become more specific. Permanently installed lighting in habitable spaces must have either manual dimming or automatic shutoff controls that turn lights off within 20 minutes after occupants leave.  
  • Utility Spaces: Garages, unfinished basements, laundry rooms, and utility rooms require automatic shutoff controls.  
  • Exterior Lighting: New limits establish the maximum amount of power that can be used for exterior lighting. 

These provisions may require additional coordination between design teams and builders to ensure that fixture selection and controls meet energy code requirements during design rather than deferred to after installation.

5. Electric Vehicle Charging Infrastructure (Appendix RE)

Delaware adopted Appendix RE, establishing electric vehicle (EV) charging infrastructure requirements for new residential construction. These requirements go beyond simply preparing buildings for potential future installations. 

New one- and two-family dwellings and townhouses with designated garages or qualifying private parking must provide one EV-ready or Electric Vehicle Supply Equipment (EVSE) space per dwelling unit. For multifamily R-2 building projects, EV-ready or EVSE spaces must be provided for 20% of the dwelling units or automobile parking spaces, whichever is less.  

Electrical distribution capacity, circuit requirements, and designated parking locations must also be accounted for in the construction documents. 

Developers and electrical designers should take these requirements into consideration early in planning, as they can affect electrical service sizing, panel capacity, parking layouts, and overall project costs. 

Key Changes to the DE Commercial Energy Code 

Delaware has adopted the 2024 IECC commercial provisions and ASHRAE 90.1-2022, with Appendix CB – Solar-Ready Zone. Project teams have the option of using either a prescriptive pathway or a performance pathway. The following changes are particularly important for teams planning commercial and 4+ story multifamily building projects.

1. Envelope Leakage Testing (Section C402.6.2.1, ASHRAE Section 5.4.3.1)

The 2024 IECC and ASHRAE 90.1-2022 introduce new commercial building envelope air leakage requirements, including mandatory whole-building blower door testing and associated documentation needed to demonstrate compliance. The code establishes a maximum air leakage rate of 0.35 cfm/ft². Under ASHRAE 90.1-2022, buildings over 10,000 sq. ft. have more flexibility in how compliance is achieved with an additional option to perform envelope commissioning in lieu of air leakage testing. 

For project teams, this makes early coordination of air barrier design, installation, and testing especially important. Envelope continuity should be considered throughout construction rather than addressed only when the building is ready for testing.

2. Renewable Energy Requirements (Section C405.15, ASHRAE Section 11.5.1)

The updated IECC and ASHRAE 90.1 standard require on-site renewable electricity generation with a minimum rated capacity of 0.75 watts per square foot (.50 watts under ASHRAE 90.1-2022), multiplied by the gross conditioned floor area of the building, up to the combined area of the three largest floors. This requirement introduces additional design and cost considerations for commercial projects, particularly those with limited available roof space or significant rooftop equipment. 

Projects that cannot accommodate the required on-site renewable generation may qualify for alternative off-site compliance provisions, subject to applicable exceptions and requirements. 

The main exceptions include: 

  • Smaller projects: New construction or additions where the combined gross conditioned floor area of the three largest floors is less than 5,000 sq. ft. under IECC 2024 or 10,000 sq. ft. under ASHRAE 90.1-2022.  
  • Limited usable roof space: More than 80% of the roof area is covered by qualifying equipment or other listed uses, such as planters, vegetated space, skylights, or occupied roof decks. 
  • Significant shading: More than 50% of the roof is shaded from direct sunlight by natural objects or structures outside the building for more than 2,500 hours annually. 
  • Alterations: Alteration projects that do not include additions are exempt.

Performance pathways and energy modeling may provide greater flexibility in evaluating overall building performance. Teams should evaluate available roof area, shading, building orientation, and renewable energy options early in design to understand the potential cost and compliance implications.

3. Commissioning Requirements Expanded (Section C408.2, ASHRAE Section 4.2.5)

The 2024 IECC/ASHRAE 90.1-2022 expands commissioning requirements, placing a greater emphasis on documenting and verifying that building systems operate as intended. The updated code adds functional testing requirements for automatic receptacle controls and expands testing provisions for lighting controls.

Commissioning of mechanical systems and service water heating remains required, with the updated code providing more specific direction on the equipment and functions that must be tested, as well clearly defining documentation needed to demonstrate compliance. 

A commissioning plan must be developed by a qualified provider and must include: 

  • A narrative description of all activities that will be accomplished, along with the personnel responsible 
  • A list of the specific equipment, appliances or systems to be tested, along with a description of the tests to be performed 
  • Functions to be tested including, but not limited to, calibrations and economizer controls 
  • Conditions under which the test will be performed, and testing shall affirm winter and summer conditions 
  • Measurable criteria for performance 

There are minor differences between the commissioning requirements in the 2024 IECC and ASHRAE 90.1-2022. Most notably, ASHRAE 90.1-2022 requires a design plan review as part of the commissioning process.  

Regardless of the compliance pathway, early coordination with a commissioning provider like ReVireo helps ensure requirements are addressed throughout the project, reducing the risk of unnecessary delays and added costs.

4. Energy Efficiency Credits (Section C406, ASHRAE Section 11.5.1)

The 2024 IECC/ASHRAE 90.1-2022 introduce additional energy efficiency credit requirements for projects using a prescriptive compliance pathway. Rather than relying solely on baseline prescriptive requirements, projects must earn additional credits by incorporating qualifying efficiency measures from designated categories. 

Available measures address areas such as the building envelope, HVAC systems, service water heating, lighting, and other building performance improvements. The number of credits required varies based on building type and occupancy, so project teams must evaluate the applicable credit targets and available measures early in design. 

This adds another layer to the compliance process, requiring architects, engineers, and energy consultants to coordinate system selections and design decisions to meet the applicable credit requirements. COMcheck documentation may also require additional supporting information to demonstrate compliance.

5. Solar-Ready Zone Requirements (Appendix CB)

Commercial buildings with 5 stories or less as well as 4 and 5-story multifamily buildings must comply with solar-ready requirements under Appendix CB. These provisions require a designated solar-ready zone covering generally 40% of the qualifying roof area, identification of the zone on construction documents, a pathway for future electrical conduit, and reserved space at the electrical service equipment for future photovoltaic (PV) systems. While these requirements prepare buildings to accommodate a future solar installation, they do not require solar panels to be installed. 

Final Thoughts  

Delaware’s final 2024 IECC adoption ultimately landed closer to a conventional code update than the transformative “zero net energy capable” framework initially proposed. Even so, the updated code represents a meaningful increase in energy efficiency requirements and signals the continued regional movement toward electrification readiness and higher-performing buildings, in line with the direction of other nearby states like New York, New Jersey, and Pennsylvania. 

Project teams should confirm jurisdiction-specific effective dates and grandfathering provisions, while addressing new requirements early through close coordination among design professionals and energy consultants. Construction professionals should prepare field teams for updated air sealing and inspection standards, engage energy consultants early, and plan for additional construction documentation and verification requirements. 

ReVireo helps project teams in Delaware understand the new requirements, evaluate energy code compliance pathways, and reduce the risk of permitting delays or costly redesigns.  ReVireo can help you navigate the state’s updated energy code with expert consulting, energy modeling, testing, and compliance support. Contact our team to discuss your project.